UsedAutomations — TESTED SURPLUS & OBSOLETE CONTROLS

1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.

Allen-Bradley

140M-C2E-A16

Motor Protection Circuit Breaker, 3‑Pole, 0.1–0.16 A, C Frame

Allen-Bradley

From $594.89In stockDiscontinued

Product Description

This motor protection circuit breaker is designed for precise thermal‑magnetic protection of small motors within the 0.1 to 0.16 A range. It provides integrated overload and short‑circuit protection with trip class 10 performance, supporting AC-3 motor starting applications. The device features a three‑pole configuration with screw main terminals and a rotary operator, suitable for DIN rail installations. With a rated frequency of 50/60 Hz and an insulation voltage up to 690 V per IEC, it achieves up to 100 kA short‑circuit breaking capacity under IEC conditions and coordinates with 100‑C and 100‑K contactors for UL Type E/F combinations. The unit carries IP2X protection, differential phase‑loss protection, and fixed magnetic release at approximately 13× In. Mechanical durability is rated at 100,000 operations, with environmental robustness for shock, vibration, and humidity per IEC test standards. Dimensions are compact at 45 × 70 × 90 mm, supporting panel density and easy integration in coordinated motor control assemblies. Packaging is single pack.

Key Features

  • Adjustable 0.1–0.16 A thermal setting
  • Three pole thermomagnetic protection
  • 100 kA IEC short circuit capacity
  • Trip class 10 with phase loss protection
  • Compact 45 x 70 x 90 mm footprint
  • IP2X degree of protection
  • Coordinates with 100‑C09 and 100‑K05 contactors

Buy Options

Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.

New

Price: $818.1
Availability: 27 in stock
Lead time: ~2 day lead

Never Used

Price: $727.2
Availability: 4 in stock
Lead time: ~6 day lead

Used

Price: $594.89
Availability: 19 in stock
Lead time: ~2 day lead

Specifications

Type
Motor Protection Circuit Breaker
Current range
0.1–0.16 A
Poles
3
Trip type
Thermal magnetic, class 10
Rated frequency
50/60 Hz
Rated insulation voltage (Ui)
690 V per IEC
Short circuit capacity (Icu)
100 kA per IEC
Utilization category
AC‑3 (IEC 60947‑4‑1)
Protection type
Adjustable thermal / fixed magnetic ~13× In
Phase loss protection
Differential release
Degree of protection
IP2X
Mechanical life
100,000 operations
Dimensions
45 x 70 x 90 mm (W x D x H)
Contactor coordination
100‑C09 and 100‑K05 per UL 508 Type E/F
Frame size
C, 32 A
Packaging
Single pack
Operating temperature
−25 °C
Storage temperature
−40 °C
Shock
30 G, 11 ms, all axes (IEC 60068‑2‑27)
Vibration
5 G (IEC 60068‑2‑6)
Part #
140M-C2E-A16
Category
Circuit Breaker
Subcategory
Molded Case Circuit Breaker
Weight
0.26 lbs
Frame/Rating
Frame C, Rating - 32 amp
Interrupting Rating/Breaking Capaci
Normal Break
Protection Type
Adj Thermal/ Fixed Mag
Current Range
Range - 0.10-0.16 Amp

Before we quote this part

Actual photos when available

Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.

Test notes for used units

Power-on or function test status is stated when available, with clear condition grading.

Trackable global shipping

DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.

Clear DOA boundary

For tested units, quote terms can include 7-day DOA support unless otherwise stated.

Independent sourcing disclaimer

We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.

Need 140M-C2E-A16 availability?

Prices and stock can change. Submit quantity, required condition, and destination for a current quote.

Request Quote

FAQ

Q: What motor current range does this breaker protect?

A: It covers adjustable thermal settings from 0.1 to 0.16 A.

Q: How many poles does the device have?

A: It is a 3‑pole motor protection circuit breaker.

Q: What is the short‑circuit rating?

A: Up to 100 kA per IEC, with UL coordination options for 65 kA at 480Y/277 V.

Q: Does it include phase loss protection?

A: Yes, it features differential phase‑loss protection.

Q: What are the physical dimensions?

A: 45 mm wide, 70 mm deep, and 90 mm high.