What types of signals does IC200ALG261 accept?
Eight differential voltage inputs within −10 to +10 V DC
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Fanuc
IC200ALG261
Fanuc
The IC200ALG261 is an 8‑channel differential analog input module designed for VersaMax systems, providing 15‑bit resolution for precise voltage measurements. It interfaces with eight differential voltage inputs and draws operating power from the backplane, eliminating the need for an external supply for the module itself; however, user transceivers require an external source. The module supports software‑configurable selection and features diagnostics to indicate loss of internal power. A continuous input logic rating of 250 VAC and a 5 V backplane with a maximum consumption of 200 mA are specified. Status monitoring is provided via LED indicators. Typical installation practices include using shielded twisted pairs for analog channels and grounding at the source device; if not feasible, grounding through the I/O module is acceptable, with optional auxiliary I/O terminal strips for additional shields. The module’s update rate is 7.5 ms, and accuracy may be affected to ±1% under severe RF interference. It is compatible with PLC CPU version 2.1 or later and Ethernet NIU EBI001 version 1.10 or later.
Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.
New
Never Used
Used
FNFP
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
Eight differential voltage inputs within −10 to +10 V DC
No, it is backplane powered; user transceivers need external power
15‑bit resolution with a 7.5 ms update rate
Yes, diagnostics indicate loss of internal power and LED status is provided
PLC CPU version 2.1 or later and Ethernet NIU EBI001 version 1.10 or later
Use shielded twisted pairs and ground at the source or through the I/O module