Q: How many analog outputs does this module provide?
A: Four single-ended voltage outputs in one group.
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Fanuc
IC200ALG322
Fanuc
This is a four-channel analog voltage output module for VersaMax systems, delivering single-ended outputs over a ±10.24 VDC range. It draws 50 mA from the +5 V backplane and requires an external user-side supply to drive the output stages. Typical use cases include precise voltage control for actuators and process signals where deterministic updates are needed; the module specifies a 0.3 ms update rate and provides status via FLD PWR and OK LEDs for quick field diagnostics. Outputs can be configured to retain last state or default on loss of backplane power or communications, with behavior managed by the CPU or NIU, and the module consumes four words of analog output data. Isolation and protective design elements are noted in supplementary materials, and recommended external supply is +18 to +30 VDC with current consumption dependent on load. Suitable for resistive loads, it integrates cleanly into VersaMax racks and supports reliable operation without thermal derating.
Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.
New
Never Used
Used
FNFP
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
A: Four single-ended voltage outputs in one group.
A: ±10.24 VDC per channel.
A: Yes, an external user-side supply is required for the outputs.
A: 50 mA from the +5 V backplane.