UsedAutomations — TESTED SURPLUS & OBSOLETE CONTROLS

Reference images are model-matched from marketplace sources and must be confirmed before purchase.

Schneider Electric

250B

Schneider Electric Compact NSX 250B Circuit Breaker

Schneider Electric

From $1,345.42In stockSource updated 6/24/2026

Product Description

Schneider Electric Compact NSX250B Circuit Breaker with MicroLogic 5.2 Control Unit Specifications: Product Type : Molded Case Circuit Breaker (MCCB) Manufacturer : Schneider Electric Model : Compact NSX250B with MicroLogic 5.2 Device Application : Distribution protection Poles Description : 3P 3d Rated Current (In) : 250 A at 40 °C Trip Unit Name : MicroLogic 5.2 E (Ammeter or Energy-metering ) Trip Unit Technology : Electronic Trip Unit Rating : 100–250 A (adjustable) Protection Type : L: Overload protection (long time) S: Short-time short-circuit protection (adjustable delay) I: Instantaneous short-circuit protection Rated Insulation Voltage (Ui) : 800 V AC 50/60 Hz Rated Impulse Withstand Voltage (Uimp) : 8 kV Rated Operational Voltage (Ue) : 690 V AC 50/60 Hz Network Type : AC Network Frequency : 50/60 Hz Breaking Capacity Code : B (25 kA at 415 V AC) Breaking Capacity (Icu) : 40 kA at 220/240 V AC 50/60 Hz (IEC 60947-2) 25 kA at 380/415 V AC 50/60 Hz (IEC 60947-2) 20 kA at 440 V AC 50/60 Hz (IEC 60947-2) 15 kA at 500 V AC 50/60 Hz (IEC 60947-2) Rated Service Breaking Capacity (Ics) : 40 kA at 220/240 V AC 50/60 Hz (IEC 60947-2) 25 kA at 380/415 V AC 50/60 Hz (IEC 60947-2) 20 kA at 440 V AC 50/60 Hz (IEC 60947-2) 15 kA at 500 V AC 50/60 Hz (IEC 60947-2) Suitability for Isolation : Yes (EN/IEC 60947-2) Utilization Category : Category A Control Type : Toggle Mounting Mode : Fixed Mounting Support : Backplate Mounting Position : Horizontal, vertical, or flat on the back Connection Type : Front connection (upside and downside) Connection Pitch : 35 mm Long-Time Pick-Up Adjustment Type (Ir) : Adjustable via dials or keypad (9 settings) Long-Time Pick-Up Adjustment Range : 100–250 A Long-Time Protection Delay Adjustment Type (tr) : Adjustable Long-Time Protection Delay Adjustment Range : 400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir Thermal Memory : 20 minutes before and after tripping Short-Time Pick-Up Adjustment Type (Isd) : Adjustable (9 settings) Short-Time Pick-Up Adjustment Range : 1.5–10 x Ir Short-Time Protection Delay Adjustment Type (tsd) : Adjustable Short-Time Protection Delay Adjustment Range : 0–0.4 s I²t ON/OFF : Selectable for short-time protection curve Instantaneous Pick-Up Adjustment Type (Ii) : Adjustable Display Type : LCD (for settings and measurements) Local Signalling : Flashing LED (green): Ready to operate LED 90 % Ir (orange): Overload pre-alarm LED 105 % Ir (red): Overload alarm Measurement Functions (MicroLogic 5.2 E): Instantaneous and demand current measurements Energy metering Kilowatt-hour metering Operational assistance (e.g., peak demand, customized alarms, operation counters) Communication : Configurable for communication with other devices (e.g., via EcoStruxure Power architecture) Mechanical Durability : 20,000 cycles Electrical Durability : 20,000 cycles at 440 V In/2 10,000 cycles at 440 V In 10,000 cycles at 690 V In/2 5,000 cycles at 690 V In Power Dissipation per Pole : 17.6 W Number of Slots for Electrical Auxiliaries : 5 slots IP Degree of Protection : IP40 (IEC 60529) IK Degree of Protection : IK07 (IEC 62262) Electrical Shock Protection Class : Class II (front face) Pollution Degree : 3 (IEC 60664-1) Ambient Air Temperature for Operation : -25 to 70 °C Ambient Air Temperature for Storage : -50 to 85 °C Relative Humidity : 0–95 % Operating Altitude : 0–2000 m without derating; 2000–5000 m with derating Standards Compliance : EN/IEC 60947-2, CCC, EAC, marine specifications Product Certifications : IEC, CCC, EAC Dimensions : Width: 105 mm (3P), 140 mm (4P) Height: 161 mm Depth: 86 mm Weight : Approximately 2.4 kg HS Code : 8536.20.90 Country of Origin : France

Buy Options

Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.

Used

Price: $1,345.42
Availability: Available to order
Lead time: Quoted after RFQ

Specifications

Category
Low-voltage Controls
Product Type
Molded Case Circuit Breaker (MCCB)
Manufacturer
Schneider Electric
Model
Compact NSX250B with MicroLogic 5.2
Device Application
Distribution protection
Poles Description
3P 3d
Rated Current (In)
250 A at 40 °C
Trip Unit Name
MicroLogic 5.2 E (Ammeter or Energy-metering )
Trip Unit Technology
Electronic
Trip Unit Rating
100–250 A (adjustable)
Protection Type
L: Overload protection (long time)
S
Short-time short-circuit protection (adjustable delay)
I
Instantaneous short-circuit protection
Rated Insulation Voltage (Ui)
800 V AC 50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Operational Voltage (Ue)
690 V AC 50/60 Hz
Network Type
AC
Network Frequency
50/60 Hz
Breaking Capacity Code
B (25 kA at 415 V AC)
Breaking Capacity (Icu)
40 kA at 220/240 V AC 50/60 Hz (IEC 60947-2)
Rated Service Breaking Capacity (Ics)
40 kA at 220/240 V AC 50/60 Hz (IEC 60947-2)
Suitability for Isolation
Yes (EN/IEC 60947-2)
Utilization Category
Category A
Control Type
Toggle
Mounting Mode
Fixed
Mounting Support
Backplate
Mounting Position
Horizontal, vertical, or flat on the back
Connection Type
Front connection (upside and downside)
Connection Pitch
35 mm
Long-Time Pick-Up Adjustment Type (Ir)
Adjustable via dials or keypad (9 settings)
Long-Time Pick-Up Adjustment Range
100–250 A
Long-Time Protection Delay Adjustment Type (tr)
Adjustable
Long-Time Protection Delay Adjustment Range
400 s at 1.5 x Ir
Thermal Memory
20 minutes before and after tripping
Short-Time Pick-Up Adjustment Type (Isd)
Adjustable (9 settings)
Short-Time Pick-Up Adjustment Range
1.5–10 x Ir
Short-Time Protection Delay Adjustment Type (tsd)
Adjustable
Short-Time Protection Delay Adjustment Range
0–0.4 s
I²t ON/OFF
Selectable for short-time protection curve
Instantaneous Pick-Up Adjustment Type (Ii)
Adjustable
Display Type
LCD (for settings and measurements)
Local Signalling
Flashing LED (green): Ready to operate
LED 90 % Ir (orange)
Overload pre-alarm
LED 105 % Ir (red)
Overload alarm
Measurement Functions (MicroLogic 5.2 E)
Instantaneous and demand current measurements
Communication
Configurable for communication with other devices (e.g., via EcoStruxure Power architecture)
Mechanical Durability
20,000 cycles
Electrical Durability
20,000 cycles at 440 V In/2
Power Dissipation per Pole
17.6 W
Number of Slots for Electrical Auxiliaries
5 slots
IP Degree of Protection
IP40 (IEC 60529)
IK Degree of Protection
IK07 (IEC 62262)
Electrical Shock Protection Class
Class II (front face)
Pollution Degree
3 (IEC 60664-1)
Ambient Air Temperature for Operation
-25 to 70 °C
Ambient Air Temperature for Storage
-50 to 85 °C
Relative Humidity
0–95 %
Operating Altitude
0–2000 m without derating; 2000–5000 m with derating
Standards Compliance
EN/IEC 60947-2, CCC, EAC, marine specifications
Product Certifications
IEC, CCC, EAC
Dimensions
Width: 105 mm (3P), 140 mm (4P)
Height
161 mm
Depth
86 mm
Weight
Approximately 2.4 kg
HS Code
8536.20.90
Country of Origin
France
Product
Energy metering

Before we quote this part

Actual photos when available

Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.

Test notes for used units

Power-on or function test status is stated when available, with clear condition grading.

Trackable global shipping

DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.

Clear DOA boundary

For tested units, quote terms can include 7-day DOA support unless otherwise stated.

Independent sourcing disclaimer

We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.

Need 250B availability?

Prices and stock can change. Submit quantity, required condition, and destination for a current quote.

Request Quote

FAQ

Is 250B discontinued?

250B is commonly available as a spare part. Submit an RFQ for pricing and lead time.

How do I buy 250B?

Submit a Request for Quote on this page with quantity, required condition, and ship-to country. We respond by email with pricing and delivery options.

What condition options are available for 250B?

We list Used for 250B (indicative availability and pricing — confirm on RFQ). See our condition policy at https://www.usedautomations.com/condition-codes.